Impact of Shunt-flexible AC Transmission System on Distance Protection of transmission Lines

Show simple item record

dc.contributor.author Sidahmed, Abubaker Hashim
dc.contributor.author Supervisor ,- Abdelaziz Yousif Mohamed
dc.date.accessioned 2014-05-08T10:21:45Z
dc.date.available 2014-05-08T10:21:45Z
dc.date.issued 2012-05-01
dc.identifier.citation Sidahmed,Abubaker Hashim.Impact of Shunt-flexible AC Transmission System on Distance Protection of transmission Lines/Abubaker Hashim Sidahmed;Abdelaziz Yousif Mohamed.-Khartoum:Sudan University of Science and Technology,College of Engineering,2012.-75p. : ill. ; 28cm.-M.Sc. en_US
dc.identifier.uri http://repository.sustech.edu/handle/123456789/4861
dc.description Thesis en_US
dc.description.abstract In recent years, a new technology – Flexible AC Transmission Systems (FACTS) is introduced in the power system. This technology could increase the transmission line capability, control the power flow, and enhance the transient stability of the power system effectively. Due to the injection of the FACTS components; the line parameters of transmission system will be changed. Therefore, the power system protection relay’s operation will be influenced. This dissertation explores an apparent impedance calculation procedure for transmission line incorporating Static Synchronous Compensator (STATCOM) (which is a vigorous component of FACTS) based on the power frequency sequence circuits. A detailed model of 6 pulses STATCOM and its control and a mho relay model are proposed and integrated into the transmission system using Power Systems Computer Aided Design (PSCAD) software. The simulation results of the application of conventional distance relay for the protection of transmission line incorporating STATCOM are presented. The simulation results carried out by PSCAD software and the analytical calculations show the impact of STATCOM on the distance protection relay during the different fault condition. The influence of location of STATCOM, the setting of STATCOM's reference voltage and the operation mode of STATCOM on mho distance relay are studied as well. The results are presented in relation to a typical 220kV, 450Km (Atbara- Portsudan) transmission system employing midpoint. III STATCOM at the en_US
dc.description.sponsorship Sudan University of Science and Technology en_US
dc.language.iso en en_US
dc.publisher Sudan University of Science and Technology en_US
dc.subject Electrical Engineering en_US
dc.subject Power en_US
dc.subject Shunt - Flexible en_US
dc.subject Transmission Lines en_US
dc.title Impact of Shunt-flexible AC Transmission System on Distance Protection of transmission Lines en_US
dc.title.alternative ‫أثر نظام نقل التیار المتردد المرن في الحمایة المسافیة لخط النقل‬ en_US
dc.type Thesis en_US