dc.identifier.citation Altayb, Ahmed Babiker Mustafa.Study the Effect of Thermal Insulation Materials on TheBuildingsupon Air Conditioning System/Ahmed Babiker MustafaAltayb,Mohammed SaifeeldinDaffallah Mohammed;EihabAbdelraouf Mustafa Omer.-Khartoum : Sudan University of Science and Technology, College of Engineering,2017.-75 p. :ill;28cm.- Bachelors search. en_US
dc.identifier.uri http://repository.sustech.edu/handle/123456789/19867
dc.description Bachelors search en_US
dc.description.abstract Thermal loads have been measured for a sample Hall (1)from Sudan University of Science and Technology, based on mathematical models and HAP software. The measurement was based on comparison when without any thermal insulation material used in the wall and roof, and use one of material from three difference of thermal insulation(10cm thickness) in wall and roof (Extruded polystyrene material, Spray polyurethane material, Air cavity) . The decremental has been calculated wall load and roof load which led to decrease in annual operational cost, and results are shown below: - The first once (without any thermal insulation material), the thermal load was 166.76Kw. - The second once (Extruded polystyrene), the difference in thermal load was 53.9Kw, which led to decrease in annual operational cost with percentage (32.32%) out of total annual operational cost. - The third once (Spray polyurethane), the difference in thermal load was 56Kw, which led to decrease in annual operational cost with percentage (33.58%) out of total annual operational cost. - The fourth once (Air cavity), the difference in thermal load was 28.24 Kw, which led to decrease in annual operational cost with percentage (16.99%) out of total annual operational cost. en_US
dc.description.sponsorship Sudan University of Science and Technology en_US
dc.language.iso en en_US
dc.publisher Sudan University of Science and Technology en_US
dc.subject Air Conditioning en_US
dc.subject Thermal Insulation en_US
dc.subject Thermal Insulation Materials en_US
dc.title Study the Effect of Thermal Insulation Materials on TheBuildingsupon Air Conditioning System en_US
dc.title.alternative دراسة تأثیر العوازل الحراریة في المباني على أجھزة التكییف en_US
dc.type Thesis en_US


Files in this item

This item appears in the following Collection(s)

Show simple item record

Share

Search SUST


Browse

My Account