Evaluation of Earthing System in some of Khartoum State Hospital

Show simple item record

dc.contributor.author Eltoom, Eman Abd elhameed Mohamed
dc.contributor.author Supervisor - Alnazier Osman Mohammed Hamza
dc.date.accessioned 2015-06-04T10:14:06Z
dc.date.available 2015-06-04T10:14:06Z
dc.date.issued 2015-02-01
dc.identifier.citation Eltoom ,Eman Abd elhameed Mohamed .Evaluation of Earthing System in some of Khartoum State Hospital /Eman Abd elhameed Mohamed Eltoom ;Alnazier Osman Mohammed Hamza .-khartoum :Sudan University of Science and Technology ,Engineering ,2015 .-64p. :ill. ;28cm .-M.Sc. en_US
dc.identifier.uri http://repository.sustech.edu/handle/123456789/10954
dc.description Thesis en_US
dc.description.abstract The importance of this study being discussed offer one of the most important electrical safety requirements (electrical grounding) in health care facilities, where the lack of grounding system in these important facilities leads to damage and electrical hazards (damages in medical devices lead to a wrong diagnosis or treatment, burns, Electric shocks to the patient and the device’s user ). The purpose of this study is to evaluate the application of the grounding system in hospitals and find out the reasons for the absence of such regulations on these important facilities and then search for solutions to these reasons. Sixteen hospitals have been surveyed (Three in Khartoum state and thirteen hospitals in different states), using a checklist designed by the researcher as a first stage and then the results were analyzed using the statistical program SPSS. In the second stage, the researcher conducted field visits to do a visual scan for seven hospitals to determine the current status of the application of grounding systems. The third and final stage is to search for an alternative metal to pure copper used in the wedge grounding in attempt to reduce the cost of the grounding system. The results showed that most of the hospitals that have been surveyed either had not contain a grounding system, or the grounding system does not function because it's old or due to not knowing it's place , in some cases the system exists and is enabled but doesn't meet all the need for the hospital .also the researcher has reached to the possibility of using steel metal after painted electrochemically with copper instead of using pure copper earthing system, which led to reduce the cost of rod from 800 pound to 50 pound. en_US
dc.description.sponsorship Sudan University of Science and Technology en_US
dc.language.iso en en_US
dc.publisher Sudan University of Science and Technology en_US
dc.subject Biomedical Engineering en_US
dc.subject Grounding System en_US
dc.subject Khartoum - Hospital en_US
dc.title Evaluation of Earthing System in some of Khartoum State Hospital en_US
dc.title.alternative تقويم وتطبيق نظام التأريض في بعض مستشفيات ولاية الخرطوم en_US