Please use this identifier to cite or link to this item: https://repository.sustech.edu/handle/123456789/21811
Title: Study of Short Circuit Faults-Case study Sudanese National Grid
Other Titles: دراسة أعطال دائرة القصر- دراسة حالة الشبكة القومية السودانية
Authors: Dawood, Alnazeir Hamad Ali
Gebriel, Mohammed Abdelrahman Mohammed
Mohammed, Mohammed Alhadi Balal
Mohammed, Mohammed Jalal Mustafa
Supervisor, -Mohammed Osman Hassan
Keywords: Short Circuit Faults
Case study Sudanese National Grid
Sudanese National Grid
Issue Date: 1-Oct-2018
Publisher: Sudan University of Science and Technology
Citation: Dawood, Alnazeir Hamad Ali .Study of Short Circuit Faults-Case study Sudanese National Grid/Alnazeir Hamad Ali Dawood...{etal};Mohammed Osman Hassan.-Khartoum: Sudan University of Science and Technology , College of Engineering , 2018.-75 p. :ill;28cm.- Bachelors search.
Abstract: In the previous period, the national grid experienced many changes represented in the addition of Merawi power station and the addition of so many new stations. This extension required the calculation of short circuit levels to determine the ratings of protective devices and to ensure the safety of power system components. Short circuit levels were calculated for all buses according to IEC-60909 standard using ETAP 16.0 program. Most of the calculated fault levels were realistic and acceptable, these values were compared with the existing ratings of circuit breakers and most of the values were satisfactory except at eleven buses where the short circuit levels exceeded the ratings of the associated circuit breakers.
Description: Bachelors search
URI: http://repository.sustech.edu/handle/123456789/21811
Appears in Collections:Bachelor of Engineering



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.