dc.date.issued2014
dc.identifier.citationAbbas, Abdelaziz Yousif Mohamed . Impact of Static Synchronous Compensatoron Performance of Distance Protection of Transmission Lines \ Abdelaziz Yousif Mohamed Abbas, Giddani Osman Addlan Kalcon,Abubaker H. Sidahmed .- Journal of Engineering and Computer Sciences (ECS) .- vol 15 , no1.- 2014.- articleen_US
dc.identifier.issnISSN 1605-427X
dc.identifier.urihttp://repository.sustech.edu/handle/123456789/16580
dc.descriptionarticleen_US
dc.description.abstractThe effect of static synchronous compensator (STATCOM) installed at transmission line on the performance of distance protection is investigated in this paper. The paper explores an apparent impedance calculation procedure for transmission line incorporating STATCOM based on the power frequency sequence circuits. A detailed model of 6 pulses STATCOM and its control and a mho relay model are proposed and integrated into the transmission system. The paper investigates distance protection operation of transmission lines with STATCOM connected at the midpoint during several operation conditions. Installation of STACTOM in the midpoint to control the reactive power flow affects the operation accuracy of distance relays. The simulation results of distance relays for the protection of transmission line incorporating STATCOM are presented. The analytical calculations show the impact of STATCOM on the distance protection relays during the different faults conditions. The study is carried-out using PSCAD/EMTC software.en_US
dc.description.sponsorshipSudan University of Science and Technologyen_US
dc.language.isoen_USen_US
dc.publisherSudan University of Science and Technologyen_US
dc.subject:STATCOM, Distance Relay, Voltage Source Converter, Flexible Ac Transmission Line and Transmission Line Protectionen_US
dc.titleImpact of Static Synchronous Compensatoron Performance of Distance Protection of Transmission Linesen_US